Parameter Viewer

Document ID ca-bc-mwqccpf-null Title MAINTAINING WATER QUALITY AT CONCRETE AND CONCRETE PRODUCTS FACILITIES URL https://www2.gov.bc.ca/assets/gov/environment/waste-management/industrial-waste/industrial-waste/concrete/maintaining_water_quality_at_concrete_facilities.pdf Jurisdiction /ca/bc Subdomain(s) Industrial water, Wastewater, Stormwater Language en Status completed Analyzed at 2026-03-15 10:21:46.872858+00:00 Relevance Defines discharge limits and monitoring for concrete facility wastewater.

Q Qualitative Requirements (6)

Req ID Category Intent Legal Status Name Subdomain(s) Context Conditions Confidence
#Q001operationaloperationalrecommendedStringent Controls Near Open Waterwastewater, otherTHE PRESENCE OF OPEN WATER NEAR A SITE SHOULD RESULT IN MORE STRINGENT CONTROLS OF PROCESS OR STORM WATER DRAINAGEPresence of open water near a sitehigh
#Q002operationaloperationalmandatoryWaste Concrete Disposalwastewater, otherWaste concrete must be disposed of so as not to cause pollution.high
#Q003prohibitionoperationalmandatoryProcess Water Discharge to GroundwastewaterProcess water from a concrete or concrete products facility can only be discharged to: - The ground if it does not cause ground water pollution.Discharging process water to the groundhigh
#Q004treatmenttreatmentmandatoryProcess Water Discharge to Surface Waterswastewater, aquatic lifeProcess water from a concrete or concrete products facility can only be discharged to: - Surface fresh or marine waters if it and any surface runoff from the facility passes through an effluent treatment system (inspected monthly to verify it is in good working order) so that the effluent has: pH 6.5 to 9.0; maximum suspended solids of 75 mg/L or total extractable hydrocarbon of 15 mg/L; and is non-acutely toxic to rainbow trout at 100% concentration during a 96-hour bioassay.Discharging process water to surface fresh or marine watershigh
#Q005monitoringreportingmandatoryRunoff Sampling and AnalysiswastewaterProcess and facility runoff must be sampled and analyzed on a minimum monthly basis, with appropriate records developed of the information.high
#Q006administrativereportingmandatoryRecord MaintenancewastewaterRecords must be maintained for a minimum five-year period.high

P Quantitative Requirements (12)

Req ID Category Intent Legal Status Name Subdomain(s) Limit Type Limit Value Context Conditions Confidence
#P001physicalunknownmandatorypHwastewaterrequirement6.5 to 9.0 pHEffluent discharge to surface fresh or marine waters from a concrete or concrete products facilityPasses through an effluent treatment system inspected monthlyhigh
#P002physicalunknownmandatorysuspended solidswastewaterMAC75 mg/LEffluent discharge to surface fresh or marine waters from a concrete or concrete products facilityPasses through an effluent treatment system inspected monthlyhigh
#P003chemicalunknownmandatorytotal extractable hydrocarbonwastewaterMAC15 mg/LEffluent discharge to surface fresh or marine waters from a concrete or concrete products facilityPasses through an effluent treatment system inspected monthlyhigh
#P004unknownunknownmandatoryacutely toxic to rainbow troutwastewaterrequirement100 % concentrationEffluent discharge to surface fresh or marine waters from a concrete or concrete products facilityMust be non-acutely toxichigh
#P005operationaloperationalmandatoryEffluent treatment system inspection frequencywastewaterrequirement1 per monthEffluent treatment system verification to ensure it is in good working orderApplies when discharging to surface fresh or marine watershigh
#P006operationaloperationalmandatoryProcess and facility runoff sampling frequencywastewaterrequirement>= 1 per monthSampling and analysis of process and facility runoffApplies to process and facility runoffhigh
#P007operationalreportingmandatoryRecord retention periodwastewaterrequirement>= 5 yearsMaintenance of sampling, analysis, and inspection recordshigh
#P008physicaltreatmentmandatoryMaximum suspended solidswastewaterMAC<= 75 mg/LEffluent discharge to surface fresh or marine waters from a concrete facilityAfter passing through effluent treatment systemhigh
#P009chemicaltreatmentmandatoryMaximum total extractable hydrocarbonwastewaterMAC<= 15 mg/LEffluent discharge to surface fresh or marine waters from a concrete facilityAfter passing through effluent treatment systemhigh
#P010operationalreportingmandatoryAdministrative Penalty (Record Keeping)wastewaterrequirement<= 10000 $Failure to maintain sampling, analysis, or inspection recordsBased on minimum five-year record maintenance requirementhigh
#P011operationaloperationalmandatoryAdministrative Penalty (General Compliance)wastewaterrequirement<= 40000 $Failure to meet any other individual requirements of the codehigh
#P012unknownoperationalmandatoryRainbow trout bioassay durationaquatic liferequirement96 hourEffluent toxicity testing for discharge to surface waters100% concentrationhigh

D Definitions (0)

No definitions.